Application
D50 series Circuit Breaker for equipment, the products use hydraulic magnetic technology, the latest international standards for structural design of advanced reasonable and applicable to the exchange of Pathology, AC230V/415V or DC 65V/80V/120V/125V electrical system for the overload protection circuit, short-circuit protection, but also for non-frequency fan access and the breaking use, has been widely used in communications equipment, laser equipment, railway locomotive, gasoline generators and other fields.
General specification
Type D50
Pole 1P,2P,3P
Rated current  1A-100A
Rated voltage  AC 230/415V  DC 65V/80V/120V/125V
rated short-circuit(making and breaking) capacity DC65V 3000A; AC 230V 2000A   O-CO-CO
insulation voltage 100mΩ,500V
industrial frequency 2500V/1min
natural life operating 10000 times,including operate 6000 times under the specified electric current
able to bear vibration frequency 10-55Hz 1.5mm
environment temperature -40+85
wiring mode  spiral type
standard GB17701-1999  EN60934-2001
Peculiarity of over current release
power sort 25±2℃  time(s)
1In 1.25In 1.5In 4In 6In
AC unwork 10s-120s 6s-60s 0.2s-3s 0.02s-2s
DC unwork 2s-60s 1.8s-30s 0.15s-2s 0.04s-1s
Dimension