Application
DZ47-125/NC-100H is such features as delicate appearance, light weight, excellent and reliableperformance, high breaking capacity, rapid tripping and mounted by rail. Its enclosure and com-ponents adopts high fire-retarding and shock-resistance plastic of long durability. It mainly servesfor protecting the circuits of AC 50Hz, 230V of single pole, 400V of two poles or three or fourpoles from overload or short-circuit, and also for unfrequent making and breaking electricalapparatus and lighting circuit.It conforms with the standards of IEC60947-2.
Main Technical Parameter
Type DZ47-125/NC-100H
Pole 1P 2P,3P,4P
Rated current (A) 63,80,100,125
Rated voltage (V) 230 400
Ambient temperature -5oC~+40oC
Type of instantaneous release C,D
Rated short circuit breaking capacity Icn(kA) 10
The over-current protection property
Ambient Temperature Initial Status Test Current Expected Result Expected Result NOte
40±2℃ Cold position 1.05In(In63A) t1h Non-release -
Cold position 1.05In (In>63A) t2h Non-release -
Carried out immedi-ately after previous test 1.30In(In63A) t < 1h Release Current smoothlyrises to specified value within 5s
1.30In (In>63A) t < 2h Release
-5~+40 Cold position 8.00In t0.2s Non-release -
Cold position 12.00In t< 0.2s Non-release -
Applicable conducting wire
Rated current(A) Nominal cross section of wire mm2
63A 16
80A 25
100A 35
Dimension