Application
HKC65 are applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three,four poles for protecting overload and short circuit, and rated current up to 63A. It can also beused for infrequent line conversion under the normal condition. The breaker is applicable tolighting distribution system in industrial enterprise, commercially district, high-rise building anddwelling house. It conforms with the standards of IEC60898.
Main Technical Parameter
Type HKC65
Pole 1P 2P, 3P, 4P
Rated current (A) 6,10,16,20,25,32,40,50,63
Rated voltage(V) 230 400
Ambient temperature -5~+40
Type of instantaneous release B,C,D
Rated short circuit breaking capacity Icn(KA) 6
Applicable conducting wire
Rated current(A) Norminal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16
The over-current protection property
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2 Cold position 1.13In t1h Non-release -
Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s<t<60s Release Current smoothly rises to specified value within 5s
(In32A)
Cold position 2.55In 1s<t<120s Release
(In>32A)
-5oC~+40 Cold position 3In t0.1s Non-release Type B
Cold position 5In t<0.1s Release Type B
Cold position 5In t0.1s Non-release Type C
Cold position 10In t<0.1s Release Type C
Cold position 10In t0.1s Non-release Type D
Cold position 20In t<0.1s Release Type D
Dimension