Application
DZ47-63S1 is applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three, four poles for protecting overload and short circuit, and rated current up to 63A. It can also be used for infrequent line conversion under the normal condition.The breaker is applicable to lighting distribution system in industrial enterprise, commercially district, high-rise building and dwelling house. It conforms with the standards of IEC60898.
Main Technical Parameter
Type DZ47-63S1
Pole 1P 2P,3P,4P
Rated current (A) 1,2,3,4,5,6,10,16,20,25,32,40,50,63
Rated voltage (V) 230 400
Ambient temperature -5oC~+40oC
Type of instantaneous release B       C D B      C D
Rated short circuit breaking capacity Icn(kA) 1-32A:6 4.5 1-32A:6 4.5
50-63A:4.5 50-63A:4.5
Applicable conducting wire
Rated current(A) Norminal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16

The over-current protection property
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2℃ Cold position 1.13In t1h Non-release -
Carried out immediatelyafter previous test 1.45In t < 1h Release -
Cold position 2.55In 1s < t< 60s(In32A) Release Current smoothly rises tospecified value within 5s
Cold position 2.55In 1s < t < 120s(In>32A) Release
-5~+40 Cold position 3In t0.1s Non-release Type B
Cold position 5In t < 0.1s Release Type B
Cold position 5In t0.1s Non-release Type C
Cold position 10In t < 0.1s Release Type C
Cold position 10In t0.1s Non-release Type D
Cold position 20In t < 0.1s Release Type D