Application
HKL7 Series high switch-off ability miniature circuit breaker is applicable to a line of AC 50Hz/60Hz, rated voltage 230/400V and rated current up to 63A, used for overload and short circuitprotection. It can also be used for infrequent line conversion under the normal condition.Thebreaker is applicable to industrial enterprise, commercially district, high-rise building and dwell-ing house. It conforms with the standards of IEC60898.
Main Technical Parameter
Type HKL7
Pole 1P 2P, 3P
Rated current (A) 6,10,16,20,25,32,40,50,63
Rated voltage(V) 230 400
Type of instantaneous release B,C,D
Rated short circuit breaking capacity Icn(KA) 10
Life (times) 1-32A Electric life 8000
Mechanical life 20000
Operation frequency 240 times per hour
40-63A Electric life 8000
Mechanical life 20000
Operation frequency 120 times per hour
Applicable conducting wire
Rated current(A) Nominal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16
The over-current protection property
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2℃ Cold position 1.13In t1h Non-release -
Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s<t<60s Release Current smoothly rises to specified value within 5s
(In32A)
Cold position 2.55In 1s<t<120s Release
(In>32A)
-5~+40 Cold position 3In t0.1s Non-release Type B
Cold position 5In t<0.1s Release Type B
Cold position 5In t0.1s Non-release Type C
Cold position 10In t<0.1s Release Type C
Cold position 10In t0.1s Non-release Type D
Cold position 20In t<0.1s Release Type D
Dimension
© 2020 HANKE All Rights Reserved.

rance1216

Tel

+86 577 62761766
0086-13968723118

wechat

Wechat:13968723118