Application
BKN miniature circuit breaker is applicable to a line of AC 50Hz/60Hz, 230V in singlepole, 400V in double, three, four poles for protecting overload and short circuit, and rated cur-rent up to 63A. It can also be used for infrequent line conversion under the normal condition.Thebreaker is applicable to lighting distribution system in industrial enterprise, commercially district,high-rise building and dwelling house. It conforms with the standards of IEC60898.
Main Technical Parameter
Type BKN
Pole 1P 2P, 3P, 4P
Rated current (A) 1,2,3,4,5,6,10,16,20,25,32,40,50,63
Rated voltage(V) 230 400
Type of instantaneous release B     C D B       C D
Rated short circuit breaking capacity Icn(KA) 1-40A: 6 4.5 1-40A: 6 4.5
50-63A: 4.5 50-63A: 4.5
Life (times) 1-32A Electric life no less than 6000 operations
Mechanical life (O-C) no less than 20000 operations
Operation frequency 240 times per hour
40-63A Electric life no less than 6000 operations
Mechanical life (O-C) no less than 20000 operations
Operation frequency 120 times per hour
Applicable conducting wire
Rated current(A) Nominal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16
The over-current protection property
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2 Cold position 1.13In t1h Non-release -
Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s<t<60s (In32A) Release Current smoothly rises to specified value within 5s
Cold position 2.55In 1s<t<120s (In>32A) Release
-5~+40 Cold position 3In t0.1s Non-release Type B
Cold position 5In t<0.1s Release Type B
Cold position 5In t0.1s Non-release Type C
Cold position 10In t<0.1s Release Type C
Cold position 10In t0.1s Non-release Type D
Cold position 20In t<0.1s Release Type D
Dimension